Why are there gaps in the graph plotted for Demand Side calculated flow

Why are there gaps in the graph plotted for Demand Side calculated flow

The most common cause of 'gaps' in the Demand side calculated flow graph plot is inaccurate system volume data!


During the Audit Wizard process a value for system volume was either selected or entered.  This was either assumed by SCADAR using a built in formulae to estimate system volume relational to the configured air compressors with additional user filtering provided for 'poor', 'regular' or 'generous' storage or it was a known system volume entered by the user.


To calculate Demand side flow, SCADAR uses the afore-mentioned 'system volume', the compressor tables output data as well as the system pressure data that was logged during the audit.  When the Audit is 'synced', SCADAR combines this data to derive the Demand side calculated flow.


If the System volume is inaccurate this can result in gaps in the graph plotted!  For example, if the combination of data derives a result where less air was consumed 'demand side' than was generated 'supply side', SCADAR has nowhere to put the extra air that's been falsely calculated!


To resolve this effect, return to Audit Wizard and adjust the 'system volume' data and 'RE-SYNC' your audit.  When the system volume data is equal to the actual system volume 'up-stream' of the location where the system pressure sensor was located, the false calculation and gap effect will be eradicated.  If you are unsure about the actual system volume, use trial and error until the effect is eradicated.

    • Related Articles

    • Simulation Wizard - Supply side & Demand side calculated flow

      Simulation Wizard is where SCADAR.NET Auditors and Consultants can use either the supply or demand side calculated flow simulation feature to assess the potential energy, cost and carbon savings that could be achieved by installing Metacentre system ...
    • How to build your own graphs (kW, PF, pressure, demand side flow, etc.)

      Before looking at any charts, doing simulation, or producing reports, compressor status should by checked by opening kW graph (and PF graph) for each compressor.  Go to Graph Wizard, choose Blank style on the top, select the audit, and click 'run ...
    • How do I assure accurate compressor status and calculated flow results on SCADAR.NET?

      To understand this topic, its beneficial to first understand that SCADAR.NET does not actually know 'compressor status'.  If you think about it, when the physical audit was performed, there's nothing actually logging compressor status!  Instead, ...
    • Logger, flow

      SCADAR flow logger data sheet
    • Graph Wizard - BLANK

      Graph Wizard - BLANK is the default location where SCADAR.NET Auditors or Consultants 'LAND' when navigating to Graph Wizard. From here, users can proceed to select all, one or a variety of supply side or demand side graphs for plotting.  Once a user ...